Header Tank Exchangers - Heating Exchanger

Introduction
These header tank heat exchangers can be used for marine engines as well as for various land based duties such as engine testing and development work, generator sets, fire pumps and combined heat and power systems. They incorporate a quiet zone header tank with a special deaeration feature and a pressurised filler cap. The removable tube stack is held in position by ‘O’ rings and is free to expand and contract within the cast housing, thus minimising thermal stresses. It can easily be removed for cleaning if necessary. Bowman manufacture a large range of header tank heat exchangers. There is a choice on the raw water side of single pass, two pass and three pass heat exchangers for different flow rates. There are also different end cover materials depending on whether the heat exchangers are used with fresh water, sea water or contaminated water. Bowman header tank heat exchangers can be selected from our technical program if the following information is supplied:
Heat to be dissipatedkWEngine water flowl/min
Max engine water temperature°CRaw water temperature°C
Type of raw water (ie. fresh water, sea water or contaminated water)

If the raw water flow is fixed please inform us, if not we can advise on the flow required.

We have some header tank heat exchangers which have been designed for specific engines, for more information on these please see our website www.ejbowman.co.uk
Installation

The header tank heat exchanger should be mounted with the header tank above the cylinder head level and with the engine water circuit arranged so that it is self venting on initial filling. A by-pass type thermostat should be used and arranged so that only the heat exchanger is by-passed when the engine is cold. All other components including a water jacketed exhaust manifold if fitted, any oil coolers, charge air coolers and exhaust gas heat exchangers should be so positioned in the circuit so that they always receive the full flow of the engine water pump.

Thermostats of the type used on some automotive engines, which simply interrupt the cooling water flow when the engine is cold, are not recommended. For unattended operation, automatic engine shut down equipment should be provided.

Provision should be made for cooling the engine water, oil and gas when heat recovery is not required.

Marine Header Tank Heat Exchangers

The range of Bowman marine header tank heat exchangers showing the various raw water flow options.

Single pass marineTwo pass marineThree pass marine
Part numberMax raw water flow l/minPart numberMax raw water flow l/minPart numberMax raw water flow l/min
DH090-360460
DH120-3064-160
EH100-4265-2GM180EH100-4165-285EH100-3401-254
EH200-4265-3GM180EH200-4165-385EH200-3401-354
FH100-4266-2GM270FH100-4166-2140FH100-3182-295
FH200-4266-3GM270FH200-4166-3140FH200-3182-395
FH300-4267-2GM375FH300-4167-2190FH300-3282-2125
FH400-4267-3GM375FH400-4167-3190FH400-3282-3125
FH500-4267-4GM375FH500-4167-4190FH500-3282-4125
GH200-4268-2GM†640GH200-4168-2†330GH200-3482-2†225
GH300-4268-3GM†640GH300-4168-3†330GH300-3482-3†225
GH400-4268-4GM†640GH400-4168-4†330GH400-3482-4†225
KH200-4269-3GM†975KH200-4169-3†490KH200-3071-3†325
KH300-4269-4GM†975KH300-4169-4†490KH300-3071-4†325
KH400-4269-4GM†975KH400-4169-4†490KH400-3071-5†325
JH200-4270-3GM†1400JH200-4170-3†700JH200-3335-3†460
JH300-4270-4GM†1400JH300-4170-4†700JH300-3335-4†460
JH400-4270-5GM†1400JH400-4170-5†700JH400-3335-5†460
PH200-4271-4GM†2125PH200-4171-4†1050PH200-3073-4†700
PH300-4271-5GM†2125PH300-4171-5†1050PH300-3073-5†700
PH400-4271-6GM†2125PH400-4171-6†1050PH400-3073-6†700

*For units fitted with copper tubes add suffix TC to part number

†Murphy Water Level Switch can be fitted to these units

Land Based Header Tank Heat Exchangers

The range of Bowman land based header tank heat exchangers showing the various raw water flow options.

Single pass land*Three pass land*
Part numberMax raw water flow l/minPart numberMax raw water flow l/min
DH090-306460
DH120-3064-160
EH100-4265-2270EH100-4065-280
EH200-4265-3270EH200-4065-380
FH100-4266-2400FH100-4066-2140
FH200-4266-3400FH200-4066-3140
FH300-4267-2560FH300-4067-2185
FH400-4267-3560FH400-4067-3185
FH500-4267-4560FH500-4067-4185
GH200-4268-2†960GH200-4068-2†335
GH300-4268-3†960GH300-4068-3†335
GH400-4268-4†960GH400-4068-4†335
KH200-4269-3†1460KH200-4069-3†485
KH300-4269-4†1460KH300-4069-4†485
KH400-4269-4†1460KH400-4069-4†485
JH200-4270-3†2070JH200-4070-3†700
JH300-4270-4†2070JH300-4070-4†700
JH400-4270-5†2070JH400-4070-5†700
PH200-4271-4†3200PH200-4071-4†1050
PH300-4271-5†3200PH300-4071-5†1050
PH400-4271-6†3200PH400-4071-6†1050

*For units fitted with copper tubes add suffix TC to part number

†Murphy Water Level Switch can be fitted to these units

 

The range of Bowman header tank heat exchangers showing their power ratings, various water volumes and our equivalent non header tank shell and tube units.

Type
Typical engine suitabilityRaw water volumeEngine water volumeHeader tank capacityShell & tube heat exchanger
DH90 •15 200.210.80.54DC90
DH120 •20 270.281.250.9DC120
EH10040 540.451.30.9EC100
EH20050 670.62.21.32EC120
FH10060 800.853.252.08FC100
FH20090 1201.14.52.93FC120
FH300120 1601.556.554.12FG100
FH400150 20029.155.7FG120
FH500190 2552.411.47.5FG140
GH200180 2403.110.96.2GL140
GH300250 3353.814.858.54GL180
GH400320 4284.618.111.24GL240
KH200360 4826.318.813GK190
KH300450 6007.525.617.33GK250
KH400550 737933.522.56GK320
JH200550 7378.827.218.56JK190
JH300700 93810.436.924.8JK250
JH400850 114012.546.332.26JK320
PH200950 127318.64934.24PK250
PH3001200 160821.86444.63PK320
PH4001400 187625.38156.43PK400

Maximum working raw water pressure 15 bar
Maximum working engine water pressure 1 bar (Filler cap rating dependant)
Maximum working temperature 110°C
*This column shows the equivalent shell and tube heat exchanger. If this type is required instead of a header tank heat exchanger, please contact us for further details of full part numbers.