Industrial Heat Exchanger - Bowman Heat Exchangers Installation. Service & Maintenance Workshops

Installation. Service & Maintenance Workshops

When you buy one of our Bowman Heat Exchangers it doesn’t end there. We support you with Maintenance Workshops East and West Coasts of Australia . The cleaning of Exchangers/Oil Coolers by Ultrasonic means, repairs to damaged units, assembly and testing is carried out at our service centres. We’re not talking a Wash & Wire Brush here but correct disassembly, Ultrasonic cleaning, Inspection & Diagnosis by qualified Nata endorsed testers, any repairs by properly trained technicians with access to stock of genuine Bowman spares, new bolts and O Rings fitted, torqued up to specification and tested in accordance with Australian Standard 4037.

Although advice is given free of charge unfortunately the Maintenance service is not however prices are kept to a minimum as this service is offered as product support.

Service workshop West Coast (08) 9455 5933, 19 Tacoma Circuit Canning Vale, WA 6105 – East Coast (07) 3375 1566, 18 Pradella Street, Darra, Qld 4076
1.Safety
1.1 Hazards when handling the heat exchanger
BOWMAN® Hydraulic Oil Coolers are constructed to current practice and recognised safety standards. Hazards may still arise from operation, such as:
  • Injury of the operator or
  • Third parties or
  • Damage to the heat exchanger or
  • Damage to property and equipment
Any person involved with the installation, commissioning, operation, maintenance or repair of the heat exchanger must be:
  • Physically and mentally capable of performing such work
  • Appropriately qualified.
  • Comply completely with the installation instructions
The heat exchanger must only be used for its intended purpose. In the event of breakdowns which may compromise safety a suitably qualified person must always be contacted.
1.2 Approved use
BOWMAN® Hydraulic Oil Coolers are only approved for cooling hydraulic oil. Any other use unless specified by BOWMAN® is not approved. BOWMAN® declines all liability for damage associated or arising from such use.
The maximum permissible operating pressure must not exceed:
Oil (primary side) : 20 bar max.
Water (secondary side) : 20 bar max.
Applies to EC-PK three pass threaded connections only – for other versions please contact BOWMAN® for guidance.
The maximum permissible operating temperature must not exceed: Oil (primary side) : 120 Deg.C CoolingWater(secondaryside) : 110Deg.C
Variants with higher temperature and pressure ratings are available. Please contact the Sales for further details.
1.3 Potential hazards
Ensure the maximum permissible operating pressure on the primary or secondary side of the heat exchanger is not exceeded. The heat exchanger or surrounding equipment may be damaged.

NB: before the oil cooler is disconnected it must be allowed to cool sufficiently and be depressurized to prevent injury. The supply and returns to the heat exchanger should be isolated to minimise fluid loss.

2 Installation
2.1 Transport / storage
The heat exchanger must be fully drained down prior to transportation. Once drained and fully dry, the heat exchanger must only be stored indoors within a non aggressive atmosphere. The connections should be capped to avoid ingress of dirt and contaminants.
2.2 Fitting
Before fitting, the heat exchanger should be checked for visible signs of damage. The oil cooler can be positioned horizontally or vertically and should be connected in counterflow so that the fluids flow in opposite directions, as shown below:
Multiple units can be connected in parallel:
Or in series:
A filter with a maximum permeability of 2.5mm should be used prior to the inlet of each circuit of the oil cooler.
Nothing should be welded to any part of the oil cooler. Each unit has threaded holes on its underside to facilitate mounting.
2.3 Connecting the heat exchanger
Shut off all drainage valves in the flow and return pipes of the primary and secondary circuits.
When fitting the heat exchanger into the pipe work care must be taken to ensure that no debris has been introduced into the primary or secondary circuit of the heat exchanger.
Unsupported lengths of pipework should be avoided so as not to subject the heat exchanger to excessive loads.
Water side pipework diameter should not reduce to less than the connection size within a distance of 1m from the oil cooler.
Measures should be taken to isolate the oil cooler from excessive vibration.
Taper fittings are not recommended as these can split the shell and end cover castings if over tightened.
The correct length of fitting should be used as too long a fitting will damage the tubestack.
Pipework materials must be compatible with the oil cooler materials. Stainless steel sea water pipes and fittings should not be used adjacent to the heat exchanger.
If the sea water supply is taken from the ship’s main, ensure that the recommended flow rate cannot be exceeded. This will normally mean that an orifice plate must be fitted in the pipe work at least 1m before the cooler with the orifice size calculated to ensure that the maximum sea water flow rate cannot be exceeded. If these precautions are not taken, it is possible that the sea water flow rate through the cooler may be several times the recommended maximum which will lead to rapid failure.
For our oil coolers, the maximum permitted sea water flow rates are as follows:
EC range 
50 l/min. 
GK range 
300 l/min. 
FC range 
80 l/min. 
JK range 
400 l/min. 
FG range 
110 l/min. 
PK range 
650 l/min. 
GL range 
200 l/min. 
No oil cooler manufacturer can guarantee that his products will have an indefinite life and for this reason, we suggest that the cooling system is designed to minimise any damage caused by a leaking oil cooler. This can be achieved as follows:
  1. The oil pressure should be higher than the sea water pressure, so that in the event of a leak occurring, the oil will not be contaminated.
  2. When the hydraulic system is not being used, the coolers should be isolated from sea water pressure.
  3. The sea water outlet pipe from the cooler should have a free run to waste.
  4. Stainless steel seawater pipes and fittings should not be used adjacent to the oil cooler.
Three Pass Bowman Heat Exchangers 
Orifice diameter in mm for max. sea water flow
Oil Cooler SeriesMax Sea Water Flow l/min1 bar2 bar3 bar4 bar5 bar 6  bar7 bar8 bar9 bar10 bar
EC50119.58.587.57.26.86.76.56.3
FC80141211109.598.78.48.28
FG110171413121110109.89.69.3
GL20023191716151414131313
GK3002823211918171761615
JK40032272422212020191818
PK65041343128272625242323
2.4 Notes on zinc anodes
The use of zinc anodes in heat exchangers has been employed for some years, generally by manufacturers using admiralty brass tube or its variants. The purpose of the zinc anode, or zinc pencil as it is sometimes called, is to prevent dezincification of the brass alloy tubes. As such zinc anode acts sacrificially in favour of the tube.
There are a number of American and European manufacturers that use these anodes in their products. Bowman do not fit zinc anodes as the tubes used in the construction of our coolers are of copper nickel alloy and as such do not require a zinc anode. It is possible that if this anode is fitted it can actually destroy the copper oxide film built up by the tube as a natural defence which can allow the tube material to be attacked.
It is usual with the copper nickel alloys to use an iron anode which allows an iron oxide film to build up inside the tube which breaks down as a sacrificial element reducing the possibility of corrosion to the heat exchanger. In Bowman designs it is not practical to fit iron anodes as their size has to be very generous. Therefore as an alternative a piece of black iron pipework can be placed before the heat exchanger which in itself acts as sacrificial element protecting the cooler. The Royal Navy has often used this technique and when the black iron pipework corrodes, it is simply replace with a fresh piece.
We do know that some manufacturers of heat exchangers, mostly those providing copies of the better known products, often fit zinc anodes incorrectly with copper nickel alloys in error.
3 Operation
The oil cooler should be pressurized on the oil (shell) side such that it is at a higher pressure than the water (tube) side. This will ensure that if a leak occurs it will be detected by a reduction in the oil level and the oil will not be contaminated. A differential pressure of 2 bar would be sufficient.
It is essential that the following instructions are followed to prevent corrosion/erosion of the heat exchanger:
  1. Always maintain the water pH to within correct levels. The ideal water pH should be kept within 7.4 to 7.6. On no account should it fall below 7.2 or above 7.8.
  2. Maximum fluid velocityt hrough the oil cooler of 2m/s for seawater (ideal seawater flow rates are detailed on page 7) or 3m/s for fresh water must not be exceeded. If in doubt contact BOWMAN® for guidance. For shipboard installations an information sheet with orifice plate sizes is available.
  3. Minimum water velocity of 1m/s should be used.
  4. Ensure compliance with water quality and maximum permissible pressure requirements.
  5. Air must be adequately vented from both circuits.
  6. Stagnant water should not be allowed to accumulate in the oil cooler.If it is not in use for any period of time the water should be drained off.
4 Commissioning
Commissioning of the heat exchanger should not be undertaken until such time that this document has been fully read and understood.
The primary and secondary circuits of the heat exchanger must be fully closed prior to commissioning.
Adequate provision should be made to ensure that correct operating/service equipment along with personal protection (PPE) in accordance with current standards/legislation is utilised prior to the commencement of any working.
Cooling water should be introduced to the oil cooler prior to the gradual introduction of hot oil.
Both circuits should be vented initially and again when operating temperatures and pressures are reached. The system should be checked for leaks.
5 Maintenance / Repair
5.1 Winter shutdown in areas exposed to frost
Care should be taken to prevent frost damage from a winter shutdown in conditions exposed to frost. We recommend fully draining down the heat exchanger or removing the heat exchanger completely from the installation throughout the duration of the shutdown period.
5.2 General maintenance
While the unit is in operation, weekly inspection of the heat exchanger and its connections should be maintained for leaks and externally visible damage. BOWMAN® recommend that the tubestack should be cleaned and inspected annually and the o rings should be renewed at this time.
Removal of the screws around the periphery of each end cover will allow the end covers and seals to be removed. The tubestack can then be withdrawn from either end of the body.
5.3 Cleaning
Any cleaning solutions used must be compatible with the oil cooler materials. This should be confirmed with the chemical’s supplier before use.
The chemical solution can be circulated through the heat exchanger or the unit can be disassembled and the tubestack submerged in a container filled with cleaning fluid.
If necessary the fluid should be neutralized after cleaning and the unit should be flushed with fresh water and dried.
Small diameter rods and brushes for tube cleaning are available from companies such as Easy Products www.easyproductsltd.com
Replacement O rings should be fitted and the end cover bolts should be initially be hand tightened then tightened in the sequence and to the torque figures below:
Oil Cooler Series Bolt Size Torque (Nm) Oil Cooler Series Bolt Size Torque (Nm) 
EC M6 8GL Series M10 37
FC M8 22GK Series M12 54
FG M8 22JK Series M16 95
 PK Series M16 130
5.4 End cover bolt tightening sequence
End covers must be refitted in the correct orientation to ensure correct performance.
6 Potential Service Issues
6.1 Tube failures
The majority of problems facing a heat exchanger are those of corrosion or erosion on the waterside. Three common types of failure are:
a) Impingement attack (or corrosion/erosion)
This is caused by water containing air bubbles flowing at high speed through the tubes. The impingement of rapidly moving water may lead to a breakdown of the protective copper oxide film built up by the tube thus allowing corrosion/erosion. This is worse with water containing sand or grit. The effect of these conditions would be pockmarking and pinholing of the tubes.
b) Oxide corrosion
This is caused by water containing organic matter such as that found in polluted estuaries. Usually this water produces hydrogen sulphide, which is very corrosive and can cause failure of the tubes, particularly if excessive water flows are used
c) Pitting
This problem is caused by very aggressive sea water in the tubes, especially in partially filled coolers where the sea water is stagnant. Low sea water flow rates can create a high temperature rise on the sea water side. Under these conditions deposits may build or settle in the tube, allowing pitting corrosion to take place under the deposits.
This is only a brief introduction to corrosion problems. The subject is complex and the purpose of these notes is to outline in very general terms what may occur under extreme conditions.
6.2 Fault finding
Symptoms
Increase in temperature on shell side or excessive pressure loss
Pressure loss is as expected, but the temperature of the oil rises
Oil leaking into the cooling water circuit or vice versa
Inadequate performance
Possible Causes
Oil sludging, tube scaling or build up of both resulting in an insulating film covering the tubes
Film, scale or restrictions on the inside of the tubes
Split or perforated tubes
Flow rates too low. Unit connected in parallel flow
Remedy
The complete heat exchanger should be thoroughly cleaned
The complete heat exchanger should be thoroughly cleaned
Tubes should be blocked with hard wooden plugs as a temporary measure & the tubestack replaced asap

Check flow rates & increase if necessary. Reconnect in counterflow as per section 2.2 

7 Warranty
All BOWMAN® Hydraulic Oil Coolers are guaranteed against manufacturing and material defects for a period of twelve months from the date of delivery.
BOWMAN® should be contacted immediately if a unit is received damaged. No attempt should be made to repair a faulty unit as this will invalidate the warranty.
For full warranty terms, please see the BOWMAN® Conditions of Sale. A copy of which is available on request or via download from the website: www.ejbowman.co.uk
8 Spare Parts
A comprehensive stock of spare parts is always available. Details are given in the Hydraulic Oil Coolers brochure which can be downloaded from:
http://www.ejbowman.co.uk/products/HydraulicOilCoolers.htm
Please contact our sales department for price and availability or nearest stockist.
9 CE Marking Documentation
Heat exchangers are covered by the Pressure Equipment Directive 97/23/EC which is mandatory for all EU member states.. This manual is part of the compliance and points out all essential safety requirements to be observed.
BOWMAN® Hydraulic Oil Coolers fall within the Sound Engineering Practice category of the Pressure Equipment Directive 97/23/EC and as such cannot be CE marked.